Rockwell Automation Publication 1734-UM001E-EN-P - July 2013
170 Default Data Maps
1734-OA2 Output Module
Message Size: 1 Byte
1734-OA4 Output Module
Message Size: 1 Byte
1734-OB2E, 1734-OB2 Electronically Protected Output Module
Message Size: 1 Byte
Message Size: 1 Byte
1734-OB4E, 1734-OB4 Electronically Protected Output Module
Message Size: 1 Byte
7654321 0
Produces (scanner Rx) No produced data
Consumes (scanner Tx) Not used Ch1 Ch0 Channel state
Where: 0 = off, 1 = on
76543 2 1 0
Produces (scanner Rx) No produced data
Consumes (scanner Tx) Not used Ch 3 Ch 2 Ch1 Ch0 Channel state
Where: 0 = Off, 1 = On
76543 21 0
Produces (scanner Rx) Not used Ch1 Ch0 Channel status
(1734-OB2E only)
Where: 0 = no error 1 = error
76543210
Consumes (scanner Tx) Not used Ch1 Ch0 Channel
state
Where: 0 = off 1 = on
76543210
Produces (scanner Rx) Not used Ch3 Ch2 Ch1 Ch0 Channel status (1734-
OB4E only)
Where: 0 = no error 1 = error