ControlLogix™ Voltage/Current Input Module 13
Publication
1756-IN039D-EN-P - February 2003
40913-M
12
34
56
78
910
1112
1314
1516
1718
1920
2122
2324
2526
2728
2930
3132
3334
3536
+
–
+
–
Shield ground
Channel 0
Channel 3
1756-IF16 Differential voltage wiring example
IN-0
IN-1
IN-2
IN-3
IN-7
RTN
IN-4
IN-5
IN-6
IN-15
IN-8
IN-9
IN-10
IN-11
RTN
IN-12
IN-13
IN-14
i RTN-0
i RTN-1
i RTN-2
i RTN-3
i RTN-7
RTN
i RTN-4
i RTN-5
i RTN-6
i RTN-15
i RTN-8
i RTN-9
i RTN-10
i RTN-11
RTN
i RTN-12
i RTN-13
i RTN-14
Shield ground
1. Use the following chart when wiring your module in differential mode
2. When operating in 4 channel, high speed mode, only use channels 0, 2, 4 and
3. All terminals marked RTN are connected internally.
4. If multiple (+) or multiple (-) terminals are tied together, connect that tie point to
terminal to maintain the module’s accuracy.
5. Terminals marked RTN and i RTN are not used for differential voltage wiring.
6. If separate power sources are used, do not exceed the specified isolation volta
This channel: Uses these terminals: This channel: Uses these terminals:
Channel 0 IN-0 (+) & IN-1 (-) Channel 4 IN-8 (+) & IN-9 (-)
Channel 1 IN-2 (+) & IN-3 (-) Channel 5 IN-10 (+) & IN-11 (-)
Channel 2 IN-4 (+) & IN-5 (-) Channel 6 IN-12 (+) & IN-13 (-)
Channel 3 IN-6 (+) & IN-7 (-) Channel 7 IN-14 (+) & IN-15 (-)
NOTES: