Allen-Bradley 1794-IE8H Instrukcja Użytkownika Strona 124

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 146
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 123
Publication 1794-UM063A-EN-P - March 2006
E-4 Configure the 1794-IE8H Module in RSLogix 5000 Software Over the ControlNet Network
Filter Cutoff
The generic profile sets all of the filter bits to 0, which is an invalid value. You
must set these bits to a valid value or you will get a diagnostic error value of 2.
Channel Bits
0…3 [Adapter Name]:[Slot]:C.Data[0].5
[Adapter Name]:[Slot]:C.Data[0].6
[Adapter Name]:[Slot]:C.Data[0].7
4…7 [Adapter Name]:[Slot]:C.Data[1].5
[Adapter Name]:[Slot]:C.Data[1].6
[Adapter Name]:[Slot]:C.Data[1].7
Filter Cutoff Bits Description
765
000Not Valid
001Not Valid
010Not Valid
0 1 1 10 Hz (100 ms)
1004 Hz (250 ms)
1012 Hz (500 ms)
1101 Hz (1 s)
1110.5 Hz (2 s)
Przeglądanie stron 123
1 2 ... 119 120 121 122 123 124 125 126 127 128 129 ... 145 146

Komentarze do niniejszej Instrukcji

Brak uwag