Allen-Bradley 1794-IE8H Instrukcja Użytkownika Strona 87

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 146
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 86
Publication 1794-UM063A-EN-P - March 2006
Calibrate Your Module 5-19
.
Start of
calibration
Measurement
equipment is
connected to
channel x
Write calibration
command 1 or 2 to
I/O module
Is
calibration
status
erroneous?
Is
calibration
status
idle?
No
Abort by
power-cycle
No
The voltage is
measured
Write voltage
value to I/O
module with
command 4 or 6
Is
calibration
status
erroneous?
Is
calibration
status
idle?
No
Abort by
power-cycle
No
Write voltage
value to I/O
module with
command 4 or 6
The current is
measured
Write current
value to I/O
module with
command 3 or 5
Is
calibration
status
erroneous?
Is
calibration
status
idle?
No
Abort by
power-cycle
No
Calibration of this
value at this
channel is done
End
Przeglądanie stron 86
1 2 ... 82 83 84 85 86 87 88 89 90 91 92 ... 145 146

Komentarze do niniejszej Instrukcji

Brak uwag