CalAmpWirelessNetworksTechnicalSupport|Tel507.833.8819|Email[email protected] Page7of10
Whenusing“Messagetype”EtherNet/IPCIPprotocol.
Tolowertheonairtrafficuncheck“Connected”inthe“MessageConfiguration”method.
BelowisanexamplewhentheMessageTypeis"CIPDataTableRead"or"CIPDataTableWrite".Notethatthe
"Connected"checkboxshouldbeunchecked,thisisbecauseifyouleaveitchecked,thenevery
timetheMSGinstructionis
executedaCIPconnection(withCIPopenmessage)willbeestablishedandbroken(withCIPclosemessage)whichadds
unnecessarilytothenetworktraffic.
WhencommunicationbetweenControlLogix/CompactLogixandotherLogixseriesPLCs.
ThesePLCs/ControllerusuallyuseEtherNet/IPCIPunconnectedprotocoltocommunicatebetweeneachother.
Note(seebelow)thatwhentheMessageTypeis"SLCTypedRead"or"SLCTypedWrite",theLogixMSGinstructionalways
usesanUnconnectedCIP(noticethatthe"Connected"checkboxisuncheckedandgrayedout).Forexample
thisisused
whenusingPCCCencapsulatedinEtherNet/IPcommand.OthersthanreadorwriteforSLCtypesarenotdescribedinthis
document.