Publication 1734-UM011D-EN-P - May 2011
POINT I/O Module and RSLogix 5000 Software Controller Tag Reference 103
1734-IE2V
2 Channel Analog Voltage Input
Input Data Data Type Default
Value
Valid Data Values
Data Channel 0 INT 0 -32,768…32,767
Data Channel 1 INT 0 -32,768…32,767
Status Byte Channel 0 SINT 0 Bit 0 Fault
Bit 1 Calibration
Bit 2 LowAlarm
Bit 3 HighAlarm
Bit 4 LowLowAlarm
Bit 5 HighHighAlarm
Bit 6 Underrange
Bit 7 Overrange
Status Byte Channel 1 SINT 0 Bit 0 Fault
Bit 1 Calibration
Bit 2 LowAlarm
Bit 3 HighAlarm
Bit 4 LowLowAlarm
Bit 5 HighHighAlarm
Bit 6 Underrange
Bit 7 Overrange
Output Data Data Type Default
Value
Valid Data Values
None
Przeglądanie stron 116