134 Quick Start
5. In the Module Properties dialog, enter the following information.
a. Name
b. Slot
c. Comm Format
d. Electronic Keying, choose Compatible Module to verify the major
revision C, because only series C modules support EtherNet/IP.
e. Click Next on the bottom of the dialog.
f. Set the RPI to 10 ms for digital and 50 ms for analog or specialty.
6. Click Finish.
Add Another Module Under the Adapter
Use this procedure to add another module under the adapter.
1. Right-click the POINT I/O adapter under I/O configuration to add a
new module.
Your second module is in slot 2.
2. Select the module from the Module Type list, and click OK.
3. In the Module Properties dialog, enter the following information:
a. Name
b. Slot
c. Comm Format
d. Electronic Keying, choose Compatible Module.
e. Click Next.
f. Set the RPI to 10 ms for digital and 50 ms for analog or specialty.
4. Click Finish.
Continue to add modules to the adapter in this fashion until you have
added all of the POINT I/O modules connected to the 1734-AENT
adapter to the I/O Configuration tree.