1609-PSB1
Service Bypass Switch
Entire contents copyright © 2006 by Rockwell Automation corporation. All rights
reserved. Reproduction in whole or in part without permission is prohibited.
A-B and Allen-Bradley are registered trademarks of Rockwell Automation Corporation.
All other trademarks are the property of their respective owners.
90-007 rev 1
Note: Read the safety information sheet before installation.
Illustrations in this document may differ slightly from the actual hardware.
Attention: This product is for use in a controlled environment. Refer to product
specifications for environmental limits.
RACK MOUNTING
n
o Set SBP in the rack. If hardwiring is required, see Connecting Power
section before screwing into the rack.
n WALL MOUNTING
41063-300-01(1)
o Whenever possible, attach one top screw and one bottom screw into a wall stud. If stud
mounting is not possible, use an expandable wall anchor. Screws are not included; .25” x
2” lag bolts are recommended.
TOWER OPTION
n Remove screw from the top and bottom rear of both the UPS and SBP. Install tie
brackets and reattach screws.
o Unscrew and remove top cover of the
UPS.
p Attach bracket to top of UPS and SBP.
q Reattach top cover of the UPS.
Note: The 1609-SBP1, when used in conjunction with an 1609-P3000A or 1609-P5000E UPS in a tower
configuration without an external battery pack 1609-PXBP, is suitable for mounting on concrete or other
non-combustible smooth surfaces only.
41063-300-01(1)
USER CONFIGURABLE
Attention: When using an online UPS, put the UPS in automatic bypass mode before
rotating the SBP switch.
1. Normal: Power is directed from the utility outlet, through the Bypass Panel and UPS,
and to connected equipment. For use during normal UPS operation.
2. Test: Power supplied to the UPS is not output. Use when tests are being conducted on
the UPS, and connected equipment is not yet desired.
3. Bypass: Power from the utility outlet is filtered through the Bypass Panel, and to the
connected equipment. Use to bypass the UPS, when functioning improperly.
Note: While operating in ‘Test’ or ‘Bypass’ mode, power to the connected equipment is
not conditioned by the UPS. At this time, the “Equipment Protection Policy” is not valid.
IDENTIFYING THE PANEL
Service Bypass Panels will differ. Refer to chart for unit specifications.
Note: HW= Hardwire
Service Bypass
Panel
Corresponding
UPS Systems
Bypass
Input
UPS
Input
UPS
Output
PDU
Panel
1609-PSB1
1609-P3000A
1609-P3000H
1609-P5000E
1609-P8000E
1609-P10000E
HW (1Ph) HW (1Ph) HW HW
*For loads exceeding 3kVA, hardwiring is necessary.
41063-300-01(1)
x4
x4
x4
x8
Rea
r
Front
x1
x4
x8
x2
x2
x2
Przeglądanie stron 0
1 2

Podsumowanie treści

Strona 1 - Service Bypass Switch

1609-PSB1 Service Bypass Switch Entire contents copyright © 2006 by Rockwell Automation corporation. All rights reserved. Reproduction in whole or i

Strona 2 - ROUBLESHOOTING

CONNECTING POWER Warning: Do not modify inlets or outlets. The SBP and UPS plugs and receptacles should match. For more information, contact Rockwe

Komentarze do niniejszej Instrukcji

Brak uwag