Installation and Wiring 2-3
Terminal Block Wiring
Terminal Block Wiring Detail Figure 2.2
Specifications
Terminal Block TB1 and TB2 Wiring Specifications Table 2.A
➊
For single phase input applications, connect the AC input power to input terminals S (L2) and T (L3).
➋
See Table 2.B for minimum recommended branch circuit protective devices.
➌
Bulletin 160 Drives are UL Listed (see Appendix A for details) as motor overload protective devices
(IEC Class 10 overload). An external overload relay is not required
for single motor applications.
Model Screw Size Max./Min. Wire Size
mm
2
(AWG)
Max./Min. Torque
Nm (lb in)
4.0 kW (5 HP) M4 5.26 – 3.31 (10 – 12) 1.35 – 0.90 (12 – 8)
All Other Ratings M4 3.31 – 0.82 (12 – 18) 1.35 – 0.90 (12 – 8)
Required Branch
Circuit Disconnect ➊
Branch Circuit
Protective Device ➋
BR+
T/L3
S/L2
R/L1
BR–
DC+
W/T3
V/T2
U/T1
DC–
Ground Terminal/Protective Earth
Terminal Block TB1
Terminal Block TB2
Motor
➌