Troubleshooting 6-3
Possible Problems and Corrective Actions Table 6.B
Problem Corrective Action
The motor does not start No output voltage to the motor. 1. Check the power circuit.
Check the supply voltage.
Check all fuses and disconnects.
2. Check the motor.
Verify that the motor is connected properly.
3. Check the control input signals.
Verify that the Start signal is present.
Verify that the contact closure signal is present at TB3-8.
Verify that either the Run Forward or Run Reverse signal is
active, but not both.
4. Check P46 - [Input Mode].
If P46 - [Input Mode] is set to 2, only the program keypad
module Start button will start the motor
5. Cycle power or use P56 - [Reset Functions] if you changed
P46 - [Input Mode].
The drive is started but the motor is not rotating.
P01 - [Output Frequency] displays 0.0.
1. Check the motor.
Verify that the motor is connected properly.
2. Check the frequency source P06 - [Frequency Command].
Verify that a frequency signal is present at terminal block
TB3 Either a -10 to +10V signal or a 4-20 mA signal.
Verify that the Preset Frequencies are set properly.
3. Check the control input signals.
Verify that SW1, SW2 and SW3 are correct. (Refer to the chart
in Chapter 5)
4. Check the following parameter settings.
Verify that P59 - [Frequency Select] is showing the desired
frequency source.
Verify that P58 - [Internal Frequency] is set to the desired
frequency.
5. Cycle power or use P56 - [Reset Functions] if you changed
P46 - [Input Mode].
The motor is not accelerating properly. 1. Check the motor.
Verify that the motor is connected properly.
Verify that no mechanical problems exist.
2. Check the following parameter settings.
Verify that P30 - [Accel Time 1] or P69 - [Accel Time 2]
whichever is currently used is set properly.
Verify that P43 - [Current Limit] is set properly.
Verify that P38 - [Boost Volts] is set properly.
Drive will not operate in the run/forward or run reverse modes. 1. Verify that P46 - [Input Mode] is set to 1.
2. Verify that neither P73 - [Reverse Disable] nor P74 - [Analog
Select] is set to 1.
3. Verify that the power has been cycled for 1and 2 to take effect.
4. Verify that both the Run Forward and Run Reverse switches are
not closed simultaneously.
5. Cycle power or use P56 - [Reset Functions] if you changed
P46 - [Input Mode].