Rockwell Automation Publication PFLEX-AP009A-EN-P - September 2012 175
Wiring Examples Chapter 2
Figure 122 - Two-wire Control with an Analog Input Speed Reference
16
15
14
13
1
7
8
9
10
11
12
5
6
2
4
3
Analog In 1 (+)
Analog In 1 (-)
Analog In 2 (+)
Analog In 2 (+)
Pot Common
17
18
20
19
- 10V Pot Reference
+24V DC Supply
Digital Input Common
24V Supply Common
Digital Input 1
Digital Input 2
Digital Input 3
Digital Input 4
+ 10V Pot Reference
PowerFlex DC
Analog Input 3 (+)
Analog Input 3 (-)
Pot Ground
Not Used
PE Ground
Internal 0V (Grd)
• Conguration:
P1322 [Direction Mode] = 1 “Bipolar”
P70 [Anlg in1 Sel] = Speed Ref A
P71 [Anlg In1 Cfg] = +/- 10
Note: DIP switch S9 should be
set to “On”
P133 [Digital In1 Sel] is kept at its default of “Stop/CF”.
P134 [Digital In2 Sel] = 5 “Run”
- Refer to the PowerFlex DC User Manual, Publication
20-p-um001, Chapter 1: Installation and Wiring, for more
details on wiring examples.
• Scaling:
P72 [Anlg In1 Scale]
P73 [Anlg1 Tune Scale]
• View Signal Value:
P1404 [Analog In1 Value]
• View Signal Output:
P385 [Speed Ref Out]
TB1
TB2
NOTE: If your 1397 drive utilizes 115 VAC Inputs, refer to
the PowerFlex DC user manual, Appendix G for details on
the 115V AC to 24V DC I/O Converter Circuit Board.
Stop/CF
Run
22
21
20
19
18
17
15
14
13
1
7
8
9
10
11
12
23
24
5
6
2
4
3
27
26
25
30
29
28
FlexPak 3000 Regulator Board
16
Clear Fault
31
32
RUN/STOP by
user contact
Meter Out Com
Meter Out2
+24V
Run
(1)
Stop
(1)
Jog
Reverse / Forward
Auto / Man
+24VDC
Coast / Stop
(1)
Customer Interlock
(1)
Fault / Alarm Reset
+24V
Digital Input 0
(1)
Motor Thermostat
(1)
+24V
+24V Common
+10VDC (Isolated)
Analog Manual Reference (+)
Analog Manual Reference (-)
Auto Reference (+)
Auto Reference (-)
Tachometer Hi Range
Tachometer Lo Range
Tachometer Common
Meter Out1
Running (N.O.)
Alarm (N.O.)
No Fault (N.O.)
• Conguration:
P103 – [AUTO REF SELECT] = Analog
• Scaling:
P101 – [ANLG AUTO GAIN ADJ]
P100 – [ANLG AUTO SIGNAL TYPE]
P102 – [ANLG AUTO ZERO ADJ]
• View Signal Value:
P188 – [ANALOG AUTO REFERENCE]
- Refer to the FlexPak 3000 Software
Reference Manual, Publication fp3-um013,
for additional details.
(1) Require for initial startup and
operational checks. Voltage must be
present at these points during operation. In
other words, these terminals must be made.
If open, the drive will be ‘Not Ready’.
(2) RUN – Edge sensitive signal that
initiates a Run command (0 1 = Run). If
the Drive is Run, voltage may be applied to
the armature causing the motor to reach the
desired speed.
Two-wire Control, Analog Input Ref