Publication 1734-IN026A-EN-P - April 2005
Installation Instructions
POINT I/O DeviceNet Adapter
Catalog Numbers 1734-ADN, 1734-ADNX
Inside…
For This Topic See Page
Important User Information 2
Preventing Electrostatic Discharge 3
Environment and Enclosure 4
About This Manual 5
About the Adapter 5
For More Information 5
Install the Adapter 6
Install a Replacement Adapter in an Existing System 10
Wire the Adapter 12
Troubleshoot with Indicators 15
North American Hazardous Location Approval 19
European Hazardous Location Approval 20
Specifications 21
Rockwell Automation Support 28
Przeglądanie stron 0
1 2 3 4 5 6 ... 27 28

Podsumowanie treści

Strona 1 - POINT I/O DeviceNet Adapter

Publication 1734-IN026A-EN-P - April 2005Installation InstructionsPOINT I/O DeviceNet AdapterCatalog Numbers 1734-ADN, 1734-ADNXInside… For This

Strona 2

10 POINT I/O DeviceNet Adapter Publication 1734-IN026A-EN-P - April 2005Install a Replacement Adapter in an Existing SystemYour existing control ap

Strona 3 - ATTENTION

POINT I/O DeviceNet Adapter 11Publication 1734-IN026A-EN-P - April 2005For information about how to remove POINT I/O modules from the DIN rail, se

Strona 4

12 POINT I/O DeviceNet Adapter Publication 1734-IN026A-EN-P - April 2005Wire the AdapterWARNINGIf you connect or disconnect the communications cabl

Strona 5 - For More Information

POINT I/O DeviceNet Adapter 13Publication 1734-IN026A-EN-P - April 2005 NC = No ConnectionCHAS GND = Chassis GroundC = CommonV = SupplySubnet conn

Strona 6 - Install the Adapter

14 POINT I/O DeviceNet Adapter Publication 1734-IN026A-EN-P - April 2005NC NCCVVCCHASCHASV dcConnect this dc supply to the internal power bus.You c

Strona 7 - 31111-MC

POINT I/O DeviceNet Adapter 15Publication 1734-IN026A-EN-P - April 2005Troubleshoot with IndicatorsUse the status indicators to troubleshoot your

Strona 8 - Network node

16 POINT I/O DeviceNet Adapter Publication 1734-IN026A-EN-P - April 2005 Indicator Indication Probable Cause Take This ActionSystem PowerOff • Not

Strona 9 - 31112-MC

POINT I/O DeviceNet Adapter 17Publication 1734-IN026A-EN-P - April 2005AdapterStatus Off No power is applied to device. Power the adapter.Green D

Strona 10

18 POINT I/O DeviceNet Adapter Publication 1734-IN026A-EN-P - April 2005 1Maxi(mum) Backplane MAC ID is an attribute for 1734-ADNX only. This va

Strona 11 - RTB removal handle

POINT I/O DeviceNet Adapter 19Publication 1734-IN026A-EN-P - April 2005 North American Hazardous Location ApprovalThe 1734-ADN adapter has North

Strona 12 - Wire the Adapter

2 POINT I/O DeviceNet Adapter Publication 1734-IN026A-EN-P - April 2005Important User InformationSolid state equipment has operational characterist

Strona 13 - 1734-ADN

20 POINT I/O DeviceNet Adapter Publication 1734-IN026A-EN-P - April 2005European Hazardous Location ApprovalThe 1734-ADN adapter has European Haza

Strona 14

POINT I/O DeviceNet Adapter 21Publication 1734-IN026A-EN-P - April 2005Specifications Communication Interface Specifications DeviceNet Communica

Strona 15 - Troubleshoot with Indicators

22 POINT I/O DeviceNet Adapter Publication 1734-IN026A-EN-P - April 2005 Communications Interface Specifications (continued)Expansion I/O Cap

Strona 16 - Publication

POINT I/O DeviceNet Adapter 23Publication 1734-IN026A-EN-P - April 2005 DeviceNet Power Supply SpecificationsInput Voltage Rating 24V dc nom

Strona 17

24 POINT I/O DeviceNet Adapter Publication 1734-IN026A-EN-P - April 2005 General SpecificationsIndicators 3 red/green status indicatorsAdapter sta

Strona 18

POINT I/O DeviceNet Adapter 25Publication 1734-IN026A-EN-P - April 2005Isolation Voltage (Continuous - Voltage Withstand Rating)50V continuousTest

Strona 19

26 POINT I/O DeviceNet Adapter Publication 1734-IN026A-EN-P - April 2005Dimensions Inches(Millimeters)3.0H x 2.16W x 5.25L(76.2H x 54.9W x 133.4L)

Strona 20

POINT I/O DeviceNet Adapter 27Publication 1734-IN026A-EN-P - April 2005Certification3 1734-ADNX(when product is marked)CE European Union 89/336/EE

Strona 21 - Specifications

ö Publication 1734-IN026A-EN-P - April 2005 PN 957955-25Supersedes Publication 1734-IN007A-EN-P - August 2000, 1734-IN007B-EN-P - June 20

Strona 22

POINT I/O DeviceNet Adapter 3Publication 1734-IN026A-EN-P - April 2005ATTENTIONPreventing Electrostatic DischargeThis equipment is sensitive to el

Strona 23

4 POINT I/O DeviceNet Adapter Publication 1734-IN026A-EN-P - April 2005ATTENTIONEnvironment and EnclosureThis equipment is intended for use in a Po

Strona 24

POINT I/O DeviceNet Adapter 5Publication 1734-IN026A-EN-P - April 2005About This Manual Use this manual as a guide to install the adapter. The ma

Strona 25

6 POINT I/O DeviceNet Adapter Publication 1734-IN026A-EN-P - April 2005Install the AdapterTo install the adapter on the DIN rail prior to installin

Strona 26

POINT I/O DeviceNet Adapter 7Publication 1734-IN026A-EN-P - April 20053. Insert the DeviceNet network plug and tighten the holding screws. WARNIN

Strona 27

8 POINT I/O DeviceNet Adapter Publication 1734-IN026A-EN-P - April 20054. Set the node address by pressing the + and - buttons on the 2-position th

Strona 28 - Rockwell Automation Support

POINT I/O DeviceNet Adapter 9Publication 1734-IN026A-EN-P - April 20055. Slide the safety end cap to remove it. This exposes the backplane and po