OMRON Tech Note
Setting up AB Point I/O with CS1W-DRM21 1/19
Summary:
This tech note explains how to configure AB 1734-ADN Point I/O adapter for use
with the CS1 DeviceNet Scanner (Master) module.
The tools needed are:
CS1 system with CS1W-DRM21
Omron Configurator Software ver 2.10
PRO27 Handheld or CX-Programmer
Three options are available for connecting to the DeviceNet network
1. If Tool port is used, use CS1W-CN226 cable
2. If EtherNet is used, use CS1W-ETN01 or ETN11
3. If computer I/F is used, use 3G8E2-DRM21-E (PCMCIA) or 3G8F5-
DRM21-E (ISA) with proper OS drivers
AB 1734-ADN with needed 1734 I/O slices mounted
In this example, the Master module is set to DeviceNet Node #60, the 1734-ADN
is set to DeviceNet Node #1
In this example, the Tool Port Pass-thru option of the software was used.
NOTE: Always leave available Node #63. As per the ODVA Specification, all
software settable devices are to come out-of-box set to node #63, 125K
baud. Should a scanner or configuration tool already be powered up and
set to Node #63, the slave will never come on-line due to a failed duplicate
node check on start up of the device.
Przeglądanie stron 0
1 2 3 4 5 6 ... 18 19

Podsumowanie treści

Strona 1 - OMRON Tech Note

OMRON Tech Note Setting up AB Point I/O with CS1W-DRM21 1/19 Summary: This tech note explains how to configure AB 1734-ADN Point

Strona 2

OMRON Tech Note Setting up AB Point I/O with CS1W-DRM21 10/19 Software, Contd. • If your DRM21 has the left decimal point ON, the

Strona 3

OMRON Tech Note Setting up AB Point I/O with CS1W-DRM21 11/19 Software, Contd. • Now that basic connections have been made to the

Strona 4

OMRON Tech Note Setting up AB Point I/O with CS1W-DRM21 12/19 Software, Contd.

Strona 5

• Click on ‘Stop Remote I/O Communication’ • The display will change to show ‘I/O data communications not running’ and the DRM21 will flash the NS

Strona 6

OMRON Tech Note Setting up AB Point I/O with CS1W-DRM21 14/19 Software, Contd. Change the Data window as shown below and click

Strona 7

OMRON Tech Note Setting up AB Point I/O with CS1W-DRM21 15/19 Software, Contd. • Close the window • Right-click on the Adapte

Strona 8

OMRON Tech Note Setting up AB Point I/O with CS1W-DRM21 16/19 Software, Contd. • This shows the default I/O information from t

Strona 9

OMRON Tech Note Setting up AB Point I/O with CS1W-DRM21 17/19 Software, Contd. • Click ‘OK’ and the screen should look similar

Strona 10

OMRON Tech Note Setting up AB Point I/O with CS1W-DRM21 18/19 Software, Contd. • Fill in the dialog box as shown below • C

Strona 11 - Tech Note

• Click on the ‘Setup’ button, Click ‘OK’ • Click on the ‘General’ tab, Click the ‘Download’ button OMRON Tech Note Setting up AB Point I/O w

Strona 12 - OMRON

OMRON Tech Note Setting up AB Point I/O with CS1W-DRM21 2/19 Step 1 The Hardware • Set the1734-ADN thumbwheel for Node # (for

Strona 13

OMRON Tech Note Setting up AB Point I/O with CS1W-DRM21 3/19 Step 2 The Software • Start the Omron DeviceNet Configurator Soft

Strona 14

OMRON Tech Note Setting up AB Point I/O with CS1W-DRM21 4/19 Software, Contd. • When complete, the screen should look similar to

Strona 15

OMRON Tech Note Setting up AB Point I/O with CS1W-DRM21 5/19 Software, Contd. • Connect the CS1W-CN226 cable between the CS1 Tool

Strona 16

OMRON Tech Note Setting up AB Point I/O with CS1W-DRM21 6/19 Software, Contd. • If all operates normally, the blue On-Line indicat

Strona 17

OMRON Tech Note Setting up AB Point I/O with CS1W-DRM21 7/19 Software, Contd. • The 1734 Adapter must be set to the ‘Auto Start M

Strona 18

OMRON Tech Note Setting up AB Point I/O with CS1W-DRM21 8/19 Software, Contd. • Fill in the dialog box as show below • Class 312

Strona 19

OMRON Tech Note Setting up AB Point I/O with CS1W-DRM21 9/19 Software, Contd. • In order for the Adapter to make the I/O sizes av